Cable Shield
The Cable Shield is used on interior boundaries to model a braided shield layer that is geometrically thin but does not have to be electrically thin. It represents a discontinuity in the tangential electric field. Mathematically it is described by a relation between the electric field discontinuity and the induced surface current density:
where indices 1 and 2 refer to the different sides of the layer.
Cable Shield Properties
Select an Cable shield typeTube (the default), Perforated tube, or User defined. By default, the Electric conductivity σ (SI unit: S/m) uses values From material.
Enter a Cable shield radius Rcable (SI unit: m). The default is 2 mm.
Tube
Enter a Thickness d (SI unit: m). The default is 0.2 mm.
Perforated Tube
Enter a Thickness d (SI unit: m), a Number of holes per meter υ (dimensionless), and enter also a Hole radius Rh (SI unit: m). Rh must be greater than d. The default is 0.2 mm, 10, and 0.5 mm, respectively.
User Defined
Enter a Transfer impedance per meter Ztpm (SI unit: Ω/m). The default is 0.01 Ω/m.
Resonance Constraint
See the Transition Boundary Condition node, Resonance Constraint section, for all settings.
Skin Depth Calculator
See the Transition Boundary Condition node, Skin Depth Calculator section, for all settings.