Displacement Ventilation
Introduction
The present example investigates the performance of a displacement ventilation system. Given measured values for inlet velocity, inlet temperature, and heat flux, this simulation yields field configurations of air temperature and velocity that are consistent with experimental measurements and analytic global models (Ref. 1).
Model Definition
In general, there are two classes of ventilation: mixing ventilation and displacement ventilation. In displacement ventilation, air enters a room at the floor level and displaces warmer air to achieve the desired temperature. Heating sources in the room can include running electronic devices, or inlet jets of warm air. A potential issue with the displacement ventilation approach is that significant temperature variation and strong stratification may arise.
The model geometry consists of a test chamber with the dimensions 2.5 m by 3.65 m by 3 m. A warm jet enters the chamber from an inlet located at the floor center. Fresh air, at constant temperature and relatively low velocity, is supplied through a wall inlet. Heat exits the chamber through an exhaust located in the center of the ceiling. The walls of the chambers are almost perfectly insulated.
Symmetry reduces the modeling domain to half of the chamber, as shown in Figure 1. The warm jet feeds 0.028 m3/s of air at a temperature of 45 °C into the room. The temperature of the fresh air is 21 °C and has a flow rate of 0.05 m3/s.
Figure 1: The modeling domain is reduced to half the chamber size due to symmetry.
Convection of heat can be either forced or free. Forced convection occurs if
(1)
where g is the gravity (m/s2), α(1/K) is the coefficient of thermal expansion, T (K) the temperature, U (m/s) the velocity, and L (m) refers to the characteristic length. Equation 1 states that the buoyancy force is small compared to the inertial force. In such a situation, the character of the flow field is described by the Reynolds number, where ν (m2/s) is the kinematic viscosity. Natural convection occurs if Equation 1 is not fulfilled, in which case the flow field character is described by the Grashof number,
If the convective forces and buoyant forces are of the same order of magnitude, then can be interpreted as the ratio between the inertial and viscous forces. That is, when the Grashof number is large, the flow becomes turbulent.
To investigate if Equation 1 holds, the air can approximated as an ideal gas in which case α = 1/T. Furthermore, ΔT ≈ 20 K, U ≈ 1 m/s, and L ≈ 2 m. This gives
Hence, it is the Grashof number that determines whether the flow is turbulent or laminar. Using the same approximations as above:
(2)
Equation 2 clearly indicates that the flow is turbulent.
Modeling Considerations
You model the flow using the k-ω model. The main reason for using the k-ω model over the k-ε model is that former is in general more reliable when it comes to predicting the spreading rate of jets (Ref. 2).
As can be seen in Figure 1, the inlets and the outlet have been extended with small domains. This is to avoid having velocity conditions perpendicular to the no-penetration conditions of the walls, which often turns out to be numerically unstable.
Results and Discussion
Figure 2 shows a streamline plot colored by the temperature. As expected, there is a stratification at z1 m with a complicated recirculation pattern above.
Figure 2: Streamlines colored by the temperature illustrating the velocity field.
A more quantitative picture is given in Figure 3 which shows isosurfaces of the temperature field. The stratification is even more clearly visible here. The result compares well with the experimental results in Ref. 1.
Figure 3: Isosurfaces of the temperature.
Figure 4 shows a comparison of the computed and measured temperature along the line (1.25,0,0) → (1.25,0,3), that is through the center of the jet. While the computational result captures the main trend with decreasing temperature with height, it still over predicts the experimental result with 2 °C at z=2.6 m. There are two possible reasons for this. The first is, as mentioned in Ref. 1, that the test chamber is not as well insulated as intended. The other possible explanation is that the buoyancy induced production in the k and ω equations (see for example Ref. 3) must be included in order to reproduce the experimental results more accurately.
Figure 4: Plume temperature.
References
1. D. Mazoni and P. Guitton, “Validation of Displacement Ventilation Simplified Models,” Proceedings of ‘Building Simulation '97’, the Fifth International IBSPA Conference, vol.  I, pp. 233–239, International Building Performance Simulation Association (IBSPA), 1997.
2. D.C. Wilcox, Turbulence Model for CFD, 2nd ed., DCW Industries, La Canada, CA, 1998.
3. S. Tieszen, A. Ooi, P. Durbin, and M. Behnia, “Modeling of Natural Convection Heat Transfer,” Proceedings of the Summer Program 1998, Stanford: Center for Turbulence Research, 1998.
Application Library path: CFD_Module/Nonisothermal_Flow/displacement_ventilation
Modeling Instructions
From the File menu, choose New.
New
In the New window, click  Model Wizard.
Model Wizard
1
In the Model Wizard window, click  3D.
2
In the Select Physics tree, select Fluid Flow>Nonisothermal Flow>Turbulent Flow>Turbulent Flow, k-ω.
3
Click Add.
4
Click  Study.
5
In the Select Study tree, select General Studies>Stationary.
6
Global Definitions
Parameters 1
1
In the Model Builder window, under Global Definitions click Parameters 1.
2
In the Settings window for Parameters, locate the Parameters section.
3
Definitions
Variables 1
1
In the Home toolbar, click  Variables and choose Local Variables.
2
In the Settings window for Variables, locate the Variables section.
3
Define a step function to be used when prescribing initial conditions for the temperature.
Step 1 (step1)
1
In the Home toolbar, click  Functions and choose Global>Step.
2
In the Settings window for Step, locate the Parameters section.
3
In the Location text field, type 1.5.
4
Click to expand the Smoothing section. In the Size of transition zone text field, type 1.5.
5
From the Number of continuous derivatives list, choose 1.
Geometry 1
Block 1 (blk1)
1
In the Geometry toolbar, click  Block.
2
In the Settings window for Block, locate the Size and Shape section.
3
In the Width text field, type D.
4
In the Depth text field, type W.
5
In the Height text field, type 2*H.
6
Locate the Position section. In the y text field, type -W/2.
7
In the z text field, type -H.
Block 2 (blk2)
1
In the Geometry toolbar, click  Block.
2
In the Settings window for Block, locate the Size and Shape section.
3
In the Width text field, type 0.05[m].
4
In the Height text field, type 2*Hd.
5
In the Depth text field, type Ad/Hd.
6
Locate the Position section. In the x text field, type -0.05[m].
7
In the y text field, type -Ad/Hd/2.
8
In the z text field, type -Hd.
Union 1 (uni1)
1
In the Geometry toolbar, click  Booleans and Partitions and choose Union.
2
In the Settings window for Union, locate the Union section.
3
Clear the Keep interior boundaries check box.
4
Click in the Graphics window and then press Ctrl+A to select both objects.
Block 3 (blk3)
1
In the Geometry toolbar, click  Block.
2
In the Settings window for Block, locate the Size and Shape section.
3
In the Width text field, type 4[m].
4
In the Depth text field, type 4[m].
5
In the Height text field, type 4[m].
6
Locate the Position section. In the x text field, type -1[m].
7
In the y text field, type -2[m].
8
In the z text field, type -4[m].
Difference 1 (dif1)
1
In the Geometry toolbar, click  Booleans and Partitions and choose Difference.
2
In the Settings window for Difference, locate the Difference section.
3
Clear the Keep interior boundaries check box.
4
5
Find the Objects to subtract subsection. Select the  Activate Selection toggle button.
6
Block 4 (blk4)
1
In the Geometry toolbar, click  Block.
2
In the Settings window for Block, locate the Size and Shape section.
3
In the Width text field, type 3[m].
4
In the Depth text field, type 2[m].
5
In the Height text field, type 5[m].
6
Locate the Position section. In the x text field, type -0.2[m].
7
In the y text field, type -2[m].
8
In the z text field, type -1[m].
Difference 2 (dif2)
1
In the Geometry toolbar, click  Booleans and Partitions and choose Difference.
2
In the Settings window for Difference, locate the Difference section.
3
Clear the Keep interior boundaries check box.
4
5
Find the Objects to subtract subsection. Select the  Activate Selection toggle button.
6
Block 5 (blk5)
1
In the Geometry toolbar, click  Block.
2
In the Settings window for Block, locate the Size and Shape section.
3
In the Width text field, type sqrt(As).
4
In the Depth text field, type sqrt(As)/2.
5
In the Height text field, type H/2.
6
Locate the Position section. In the x text field, type D/2-sqrt(As)/2.
7
In the z text field, type -0.05[m].
Block 6 (blk6)
1
In the Geometry toolbar, click  Block.
2
In the Settings window for Block, locate the Size and Shape section.
3
In the Width text field, type sqrt(Ao).
4
In the Depth text field, type sqrt(Ao)/2.
5
In the Height text field, type 0.45[m].
6
Locate the Position section. In the x text field, type D/2-sqrt(Ao)/2.
7
In the z text field, type H-0.3[m].
Mesh Control Domains 1 (mcd1)
1
In the Geometry toolbar, click  Virtual Operations and choose Mesh Control Domains.
2
On the object fin, select Domains 2 and 5 only.
It might be easier to select the domains by using the Selection List window. To open this window, in the Home toolbar click Windows and choose Selection List. (If you are running the cross-platform desktop, you find Windows in the main menu.)
3
In the Geometry toolbar, click  Build All.
4
In the Model Builder window, collapse the Geometry 1 node.
5
Click the  Zoom Extents button in the Graphics toolbar.
The model geometry is now complete and should look like Figure 1.
Add Material
1
In the Home toolbar, click  Add Material to open the Add Material window.
2
Go to the Add Material window.
3
4
Click Add to Component in the window toolbar.
5
In the Home toolbar, click  Add Material to close the Add Material window.
Turbulent Flow, k-ω (spf)
1
In the Model Builder window, under Component 1 (comp1) click Turbulent Flow, k-ω (spf).
2
In the Settings window for Turbulent Flow, k-ω, locate the Physical Model section.
3
Select the Include gravity check box.
4
Specify the rref vector as
Enable buoyancy-induced turbulence.
Gravity 1
1
In the Model Builder window, under Component 1 (comp1)>Turbulent Flow, k-ω (spf) click Gravity 1.
2
In the Settings window for Gravity, locate the Acceleration of Gravity section.
3
Select the Include buoyancy-induced turbulence check box.
Inlet 1
1
In the Physics toolbar, click  Boundaries and choose Inlet.
2
3
In the Settings window for Inlet, locate the Velocity section.
4
In the U0 text field, type Us.
5
Locate the Turbulence Conditions section. From the IT list, choose High (0.1).
The air probably enters through a grid. It is therefore appropriate to set a high inlet intensity and short length scale.
Inlet 2
1
In the Physics toolbar, click  Boundaries and choose Inlet.
2
3
In the Settings window for Inlet, locate the Velocity section.
4
In the U0 text field, type Ud.
Outlet 1
1
In the Physics toolbar, click  Boundaries and choose Outlet.
2
3
In the Settings window for Outlet, locate the Pressure Conditions section.
4
Select the Normal flow check box.
Symmetry 1
1
In the Physics toolbar, click  Boundaries and choose Symmetry.
2
Heat Transfer in Fluids (ht)
1
In the Model Builder window, under Component 1 (comp1) click Heat Transfer in Fluids (ht).
2
In the Physics toolbar, click  Boundaries and choose Symmetry.
Symmetry 1
Select Boundary 2 only.
Temperature 1
1
In the Physics toolbar, click  Boundaries and choose Temperature.
2
3
In the Settings window for Temperature, locate the Temperature section.
4
In the T0 text field, type Tdiff.
Temperature 2
1
In the Physics toolbar, click  Boundaries and choose Temperature.
2
3
In the Settings window for Temperature, locate the Temperature section.
4
In the T0 text field, type Tsource.
Outflow 1
1
In the Physics toolbar, click  Boundaries and choose Outflow.
2
Heat Flux 1
1
In the Physics toolbar, click  Boundaries and choose Heat Flux.
2
In the Settings window for Heat Flux, locate the Heat Flux section.
3
Click the Convective heat flux button.
4
In the h text field, type 0.4[W/(m^2*K)].
5
In the Text text field, type Tout.
6
Mesh 1
Size
1
In the Model Builder window, under Component 1 (comp1) right-click Mesh 1 and choose Edit Physics-Induced Sequence.
2
In the Settings window for Size, locate the Element Size section.
3
Click the Custom button.
4
Locate the Element Size Parameters section. In the Minimum element size text field, type 0.015.
Size 1
1
In the Model Builder window, click Size 1.
2
In the Settings window for Size, locate the Geometric Entity Selection section.
3
Click  Clear Selection.
4
5
Locate the Element Size section. Click the Custom button.
6
Locate the Element Size Parameters section. Select the Maximum element size check box.
7
Size 1
1
In the Model Builder window, right-click Free Tetrahedral 1 and choose Size.
2
In the Settings window for Size, locate the Geometric Entity Selection section.
3
From the Geometric entity level list, choose Domain.
4
5
Locate the Element Size section. Click the Custom button.
6
Locate the Element Size Parameters section. Select the Maximum element growth rate check box.
7
Boundary Layer Properties 1
1
In the Model Builder window, expand the Component 1 (comp1)>Mesh 1>Boundary Layers 1 node, then click Boundary Layer Properties 1.
2
In the Settings window for Boundary Layer Properties, locate the Boundary Layer Properties section.
3
In the Thickness adjustment factor text field, type 3.
4
In the Number of boundary layers text field, type 5.
5
In the Model Builder window, right-click Mesh 1 and choose Build All.
Results
Large models may be easier to work with if the plots are updated on request only.
1
In the Model Builder window, click Results.
2
In the Settings window for Results, locate the Update of Results section.
3
Select the Only plot when requested check box.
Study 1
1
In the Home toolbar, click  Compute.
Proceed to reproduce Figure 2.
Results
Wall Resolution
1
In the Model Builder window, expand the Wall Resolution (spf) node, then click Wall Resolution.
2
In the Settings window for Surface, locate the Coloring and Style section.
3
From the Coloring list, choose Uniform.
4
From the Color list, choose Gray.
5
Click to expand the Title section. From the Title type list, choose None.
Streamline 1
1
In the Model Builder window, right-click Wall Resolution (spf) and choose Streamline.
2
In the Settings window for Streamline, locate the Data section.
3
From the Dataset list, choose Study 1/Solution 1 (sol1).
4
Locate the Streamline Positioning section. From the Positioning list, choose Uniform density.
5
In the Separating distance text field, type 0.07.
6
Locate the Coloring and Style section. Find the Line style subsection. From the Type list, choose Ribbon.
Color Expression 1
1
Right-click Streamline 1 and choose Color Expression.
2
In the Settings window for Color Expression, click Replace Expression in the upper-right corner of the Expression section. From the menu, choose Component 1 (comp1)>Heat Transfer in Fluids>Temperature>T - Temperature - K.
3
Locate the Coloring and Style section. From the Color table list, choose Thermal.
4
Click to expand the Range section. Select the Manual color range check box.
5
In the Minimum text field, type 293.
6
In the Maximum text field, type 300.
Streamline 1
1
In the Model Builder window, click Streamline 1.
2
In the Settings window for Streamline, click to expand the Title section.
3
From the Title type list, choose Manual.
4
In the Title text area, type Streamlines colored by temperature.
Streamlines
1
In the Model Builder window, under Results click Wall Resolution (spf).
2
In the Settings window for 3D Plot Group, type Streamlines in the Label text field.
Isothermal Contours (ht)
Execute the following steps to reproduce Figure 3.
Isosurface
1
In the Model Builder window, expand the Isothermal Contours (ht) node, then click Isosurface.
2
In the Settings window for Isosurface, locate the Expression section.
3
From the Unit list, choose degC.
4
Locate the Levels section. From the Entry method list, choose Levels.
5
In the Levels text field, type 22 23 24 25 26.
The following steps will reproduceFigure 4.
Table 1
1
In the Results toolbar, click  Table.
2
In the Settings window for Table, locate the Data section.
3
Click Import.
4
Table
1
Go to the Table window.
2
Click the right end of the Display Table 1 split button in the window toolbar.
3
Results
Table Graph 1
1
In the Model Builder window, under Results>1D Plot Group 6 click Table Graph 1.
2
In the Settings window for Table Graph, locate the Data section.
3
From the x-axis data list, choose Column 2.
4
Locate the Coloring and Style section. Find the Line style subsection. From the Line list, choose None.
5
Find the Line markers subsection. From the Marker list, choose Circle.
6
From the Positioning list, choose In data points.
7
Click to expand the Legends section. Select the Show legends check box.
8
From the Legends list, choose Manual.
9
Cut Line 3D 1
1
In the Results toolbar, click  Cut Line 3D.
2
In the Settings window for Cut Line 3D, locate the Line Data section.
3
In row Point 1, set x to D/2.
4
In row Point 2, set x to D/2 and z to H.
1D Plot Group 6
1
In the Model Builder window, click 1D Plot Group 6.
2
In the Settings window for 1D Plot Group, locate the Data section.
3
From the Dataset list, choose Cut Line 3D 1.
Line Graph 1
1
Right-click 1D Plot Group 6 and choose Line Graph.
2
In the Settings window for Line Graph, locate the y-Axis Data section.
3
In the Expression text field, type z.
4
Locate the x-Axis Data section. From the Parameter list, choose Expression.
5
In the Expression text field, type T.
6
From the Unit list, choose degC.
7
Click to expand the Coloring and Style section. In the Width text field, type 3.
8
Click to expand the Legends section. Select the Show legends check box.
9
From the Legends list, choose Manual.
10
1D Plot Group 6
1
In the Model Builder window, click 1D Plot Group 6.
2
In the Settings window for 1D Plot Group, click to expand the Title section.
3
From the Title type list, choose None.
4
Locate the Plot Settings section. Select the x-axis label check box.
5
6
Select the y-axis label check box.
7
8
Locate the Axis section. Select the Manual axis limits check box.
9
In the x minimum text field, type 0.
10
In the x maximum text field, type 46.
11
In the y minimum text field, type 0.
12
In the y maximum text field, type 3.
13
In the 1D Plot Group 6 toolbar, click  Plot.